Model Item |
PM-10000GT |
Inverter
Technology |
Conversion
Mode |
Sine-wave, Current source, High frequency PWM |
Isolation Method |
Transformer-less Design * |
DC Input Data |
|
Nominal DC Voltage |
740 VDC |
Max. DC input Voltage |
1000 VDC |
Working range |
300VDC~1000VDC ** |
Max DC input current (Each MPPT Tracker) |
28.6 Amp |
MPPT Range |
370 VDC ~ 850 VDC |
MPPT Tracker |
2 |
AC Output Data |
|
Nominal AC Power |
10000W |
Max. AC Power |
11000VA |
Nominal AC Voltage |
AC 230V x 3 |
Output Connect Method |
3-Phase / 4-Wires (L1, L2, L3, N, PE) |
AC Voltage Rang |
184~264.5Vac(Base on 230 Vac) |
Nominal AC Current |
43.47Amp |
Frequency |
50/60Hz Auto-Selection (47.5 ~ 51.5 Hz or 59.3 ~ 60.5 Hz) |
Power Factor |
COS PHI 0.8-1.0 |
Current Distortion |
Total Harmonic current : Less than 5%
Single Harmonic current : Less than 3% |
Efficiency Data |
|
Max. efficiency |
>97.5% |
Euro efficiency |
>97.0% |
CEC efficiency |
>97.0% |
Environmental |
|
Operating Temperature |
-20 °C ~ + 60 °C |
-4 °F ~ 139 °F |
Humidity |
0 to 100%(Without condensation) |
Altitude |
0 ~ 2000 M / 0 ~ 6600 ft |
Mechanical |
|
Dimensions
(H x W x D in mm ) |
|
Weight (Kgs / Lbs) |
|
Protection Class |
IP65, outdoor |
Cooling |
Fan-cooled |
AC Connector |
Connector |
DC Connector |
Connector |
Communication |
|
Communication Interface |
RS232 |
USB, RS485, Dry contact, TCP/IP |
Front Panel |
|
LCD |
Boost input Voltage/Boost input Current/Boost input Power/AC output Voltage /AC output frequency/AC output current /AC output power/AC Energy yield/Inner Temperature/Heat sink Temperature /Status message/ Error message |
LED |
RED |
On: Ground fault or DC input insulation fault |
Yellow |
On: Unit Error or Alarm |
Green |
Flash: Standby or Sleeping mode
On: Normal Operation |
Key Pad |
UP key/ Down key/ Function key/ Enter key |
Protection |
|
Utility |
Over/under Voltage, Over/under Frequency,
Ground fault, DC Isolation fault |
Islanding operation detection |
Passive : Voltage phase jump detection
Active : Reactive power control |
Over Temperature |
reduced output power |
Certification |
|
Safety |
VDE 0126-1-1 |
EN62109-1 |
EMI/EMC |
EN 61000-6-1, EN 61000-6-3, EN 61000-3-3 |