| Model No. |
PM-2400LC-24 |
| Output Power Continuous |
2400W |
| Max. Surge Power |
4800W |
| 1. Input Section |
| Input Nominal Voltage |
110Vac or 220Vac |
| Input Voltage Range |
60V~140Vac or 120V~280Vac |
| Line Low Transfer |
60Vac ± 2% or 120Vac ± 2% |
| Line Low Return |
65Vac ± 2% or 130Vac ± 2% |
| Line High Transfer |
140Vac กำ 2% or 280Vac กำ 2% |
| Line High Return |
130Vac ± 2% or 260Vac ± 2% |
| Input Frequency |
50Hz / 60Hz (45Hz~70Hz) |
| 2. Output Section |
| Output Voltage |
100 / 110 / 115 / 120Vac or 200 / 220 / 230 / 240Vac re-settable via LCD panel |
| Waveform |
Pure Sine Wave |
| Voltage Regulation (Batt. Mode) |
< 3% RMS for entire battery voltage range |
| Output Frequency |
50Hz or 60Hz ± 0.1Hz |
| Efficiency |
> 80% |
| Maximum Load |
Up to short circuit |
| Asymmetrical Load Max. |
Up to nominal output power |
| Overload and Short Circuit Protection |
Automatic disconnection |
| Overheating Temperature Protection |
Acoustic warning before shut-off.
Automatic restart |
| Power Factor |
0.8 |
| 3. Battery Section |
| Voltage Range |
24VDC (20~32VDC) |
| Backup Time (at full load) |
Long time available |
| Input Frequency Range |
45~70Hz |
Max. Charging Current
(3 steps selectable) |
60/80/100Amp |
| 4. Display |
| LCD Display |
UPS status, I/P&O/P Voltage Frequency, Load%,
Battery Voltage & %, Temperature, Model |
| LED Display |
Normal (Green), Warning (Yellow), Fault (Red) |
| 5. Audible Alarm |
| Battery Mode |
Beeping every 4 seconds |
| Low Battery |
Beeping every second |
| Overload |
Beeping twice per second |
| Temperature Compensation (Option) |
3mV / °C cell |
| 6. General date |
| AC By Pass Time (UPS Mode) |
< 8 ms. |
| Operation Temperature |
-20 °C to +55 °C |
| Audible Noise |
Less than 55dBA (at 1M) |
| Relative Humidity |
0-95% non-condensing |
| Dimensions (L x W x H mm) |
450 × 298 × 190 |
| Weight (by Kg/s) |
23.0 |