HOME > Products > UPS > Heaven Series (Rack Mount) 0.6K~3.0KVA > PM-322500SKER

無標題文件


Certificate
On-line Catalog

Back Panel
Character:
Line interactive design
Boost and buck AVR
Hot swappable battery replacement by users
Overload, on-line, battery status LED or LCD display
Fully digitized microprocessor controlled
Smart RS-232 communication port
Lightning and surge protection
Short circuit and overload protection
50/60Hz frequency auto sensing
Tel/modem internet spike protection
Site wiring fault warning *
Smart power management with software
Load/Battery power meter display
Advanced battery management (ABM)
Energy saving (UPS sleep mode)
Cold start (DC power on)
SNMP capability (optional)
USB capability (optional)

* Feature only for 100V/110V/115V models

Description:
Pure sine wave output for any critical load.

Specifications:
Tower Model (LED display) PM-322500SKE
Tower Model (LCD display) PM-322500SKC
19" Rack-mount Model (LED display) PM-322500SKER
19" Rack-mount Model (LCD display) PM-322500SKCR
INPUT

 

Capacity 2500VA
Voltage +/-25% at line input, single phase
Frequency 50 or 60Hz +/-5Hz (auto sensing)
OUTPUT Voltage
(on battery)
Pure sine wave at +/-5% of nominal, -10% of nominal after low battery warning
Frequency
(on battery)
50 or 60Hz +/-0.5%
Voltage Regulation (AVR) AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal.
AVR decrease output voltage 15% below input voltage if +9% to +25% of nominal
PROTECTION
& FILTERING
Spike Protection 320 Joules, 2ms
Unit Input Fuse for 110V models Except 3000A, breaker for 220V models Except 1000A
EMI/RFI filter 10dB at 0.15MHz, 50 dB at 30MHz
Overload Protection UPS automatic shutdown if overload exceeds 110% of nominal at 20 seconds and 125% at 5 seconds.
Transfer Time 2/4 milliseconds (typical), including detection time
Short Circuit UPS output cut off immediately or input fuse (or breaker) protection
BATTERY Type Hot swappable, sealed, maintenance-free lead acid, with 3-6 years lifetime
Typical Recharge Time 4 hours (to 90% of full capacity)
Protection Automatic self-test & discharge protection, Replace battery indicator
Back up Time
(one PC and one 15" monitor)
140 min
Net Weight Kg
(lbs)
Tower 30.0 (66.0 lb)
19" Rack-mount 28.4 (62.5 lb)
DIMENSION
W x D x H (mm)
Tower 170 x 450 x 226 (6.7" x 17.7" x 8.9")
19" Rack-mount 483 x 381 x 130 (19.0" x 15.0" x 5.1")
LCD Indicators Status Indicate line, bypass, inv, backup, fault, bat capacity, load capacity, I/P frequency, O/P voltage, O/P frequency, inside temperature, fault status, load
INTERFACE RS232 Detect battery low, Schedule UPS on/off, AC input/output power status display.
Dry contact Sends AC fail and battery low signals, and receives shutdown signal from computer.
Option Novell, SNMP, Windows NT, Windows 95/98/2000/ME
ALARM Battery Back-up Slow beeping sound (about 0.25Hz)
Battery Low Rapid beeping sound (about 1.00Hz)
Overload Continuously beeping sound
ENVIRONMENT Ambient Operation 3,500 meters max, elevation. 0-95% humidity non-condensing, 0-40 deg
Audible Noise <45dBA (1 meter from surface)
Storage Condition 15,000 meter max. elevation