| MODEL |
PM-51000APR |
| INPUT |
Capacity
(On Battery) |
1000VA |
| Capacity (Surge Protection outlets) |
500VA |
| Voltage |
+/-25% at line input |
| Frequency |
50 or 60 Hz +/-10% (auto sensing) |
| OUTPUT |
Voltage (on battery) |
Simulated sine wave at
100V or 110V/115V/120V or 220V/230V/240V +/-5% |
| Frequency (on battery) |
50 or 60 Hz +/-0.5% |
| Voltage Regulation (AVR) |
AVR automatically increase output voltage 15%
above input voltage if -9% to -25% of nominal.
AVR decrease output voltage 13% below input voltage
if +9% to +25% of nominal |
| Transfer Time |
2/4 milliseconds, including detection time |
PROTECTION
& FILTERING |
Spike Protection |
320 Joules |
| EMI/RFI Filter |
10dB at 0.15MHz, 50dB at 30MHz |
| Unit Input |
For overload & Short circuit protection |
| Overload Protection |
UPS automatic power off if overload exceeds 110% of
nominal at 60 seconds and 130% at 3 seconds |
| 10 Base-T Cable Port |
Network (UTP, RJ-45) compatible jacks |
| Short Circuit |
UPS output cut off immediately or input circuit breaker protection |
| BATTERY |
Type |
Sealed, Maintenancd-free lead acid |
| Typical Recharge Time |
8 hours (to 90% of full capacity) |
Back-up Time
(a PC with 15" monitor) |
50 - 60 mins |
| Protection |
Automatic self-test, Discharge protection, Replace battery indicator |
| PHYSICAL |
Net Weight Kg(lbs) |
10.5 (23.1 lb) |
| Shipping Weight Kg(lbs) |
11.7 (25.7 lb) |
| Dimension WxDxH (mm) |
483 x 362 x 44 (1U) |
| INTERFACE |
RS232 |
RS-232C Bi-directional communication port |
| ALARM |
Battery Back-up |
Slow beeping sound (about 0.47 Hz) |
| Battery Low |
Rapid beeping sound (about 1.824 Hz) |
| Overload |
Continuously beeping sound |
| ENVIRONMENT |
Ambient Operation |
3,500 meters max, elevation. 0-95% humidity non-condensing, 0-40 |
| Audible Noise |
<40dBA (1 meter from surface) |
| Storage Condition |
15,000 meter max |