| MODEL |
PM-52000AP |
| CAPACITY |
Capacity |
2000VA |
| OUTPUT |
Voltage (on battery) |
Simulated sine wave at 100V / 110V / 115V / 120V or 220V / 230V / 240V +/- 5% |
| Frequency (on battery) |
50 or 60 Hz +/-1Hz |
| Voltage Regulation (AVR) |
AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal.
AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal |
| Transfer Time |
2 / 4 milliseconds, including detection time |
| INPUT |
Voltage |
100V / 110V / 115V / 120V or 220V / 230V / 240V +/- 25% at line input |
| Frequency |
50 or 60 Hz +/- 10% (auto sensing) |
PROTECTION
& FILTERING |
Spike Protection |
480 Joules, 2ms |
| Unit Input |
Fuse or circuit breaker for overload & short circuit protection |
| Overload Protection |
UPS automatic power off if overload exceeds 110% of
nominal at 60 seconds and 130% at 3 seconds |
| 10 Base-T Cable Port |
YES |
| Short Circuit |
UPS output cut off immediately or input fuse protection |
| BATTERY |
Type |
Sealed, maintenance-free lead acid batteries with 3-6 years typical lifetime |
| Typical Recharge Time |
6 hours (to 90% of full capacity) |
Back-up Time
(a PC with 15" monitor) |
80 - 90 mins |
| Protection |
Auto discharge protection |
| PHYSICAL |
Net Weight Kg (lbs) |
15.9 (35.0) |
| Shipping Weight Kg (Ibs) |
17.3 (38.0) |
| Dimension WxDxH (mm) |
382 x 130 x 192
(15.0" x 5.1" x 7.5") |
| Input Inlet |
IEC 320 power inlet |
| Receptacles |
NEMA 5-15R(115V) / IEC 320 female appliance coupler (220V) |
| INTERFACE |
RS232 |
YES |
| ALARM |
Battery Back-up |
Slow beeping sound (about 0.47 Hz) |
| Battery Low |
Rapid beeping sound (about 1.824 Hz) |
| Overload |
Continuously beeping sound |
| ENVIRONMENT |
Ambient Operation |
3,500 meters max, elevation. 0-95% humidity non-condensing, 0-40 |
| Audible Noise |
<40dBA (1 meter from surface) |
| Storage Condition |
15,000 meter max. elevation |