HOME > Products > Solar & Wind > SI Series 1500W~6000W > PM-6000SI






Front Panel
Accessory
Remote Control
Character:
General
More inverters stackable
3 Phase connectable
Uninterrupted AC power (UPS function)
Power Control - Dealing with limited generator or shore side power
Power Assist - Boosting the capacity of shore or generator power
LCD display for parameter setting and error messages
Programming auxiliary relay (x 3)

Battery Charger
Adaptive 4-stage charge characteristic: Bulk-Absorption-Float-Equalize
The right amount of charge: Variable Absorption Time
Preventing damage due to excessive gassing: The Battery Safe Mode
Less maintenance and aging when the battery is not in use: The Equalize Mode
2 outputs to charge 2 battery banks
To increase battery life: Temperature Compensation
Battery Voltage Sense
Extensional Solar Charger Capacity expansion by max. 10 sets of solar chargers (Our Premium Series)

Description:
Stackable Inverter ~ When you need more power one day. Stack one more SI inverter to have more power.
Maximum 5pcs for each phase, 15pcs for 3phase.
3 Phase available ~ 2 or more SI inverters to have 3phase change is workable.
Solar charge controller: option and communicated with PM Premium series.
Premium series is stackable also. (Max. 10units).
PM provides off grid system at maximum 90KW inverter + 600Amp solar charge control.


Specifications:
 MODEL
PM-6000-SI-24
PM-6000-SI-48
 INVERTER
 Input Voltage Range (VDC)
19~32VDC
38~64VDC
 Output Voltage (VAC)
185~240VAC
 Output Frequency
50Hz / 60Hz ± 0.1%
 Output Voltage
Pure sine wave
 THD
< 5%
 Power Factor
All loads
 Switch-on Behavior
Nominal output voltage within 20 msec.
 Cont. Output Power at 25°C(W)
 (cos£c=1.0)
6000W
 Maximum Power (W)
12000W
 Maximum Efficiency (%)
88
 Zero-load Power (W)
20W
 CHARGER
 Input Voltage Range (VAC)
200~250VAC
 Input Frequency
45~55Hz / 55~65Hz
 Power Factor
1
 Charge Characteristic
4-stage adaptive
 Maximum DC Voltage Ripple (Vrms)
< 1.25 V
 Charge Voltage "Absorption" (VDC)
57.6V
 Charge Voltage "Float" (VDC)
55.2V
 Output Charge Voltage (VDC)
 Min.,Max.
22V,64V
 Charge Current House Battery (A)
140A
 Charge Current Starter Battery (A)
4A
 AC INPUT SWITCH
 Protected by Thermal Circuit Breaker
100A (110V) / 60A (220V)
 Switch-over Time Inverter to AC Input
0 msec.
 Switch-over Time AC Input to Inverter 
0 msec.
 Detection Time AC Input Fault
4 msec. to 10 msec.
 Trip Level Mains to Inverter
90VAC / 180VAC
 Trip Level Inverter to Mains
94VAC / 187VAC
 Min.- Max. Frequency Range
 (50Hz/60Hz)
45~55Hz or 55~65Hz
 GENERAL
 Power Control
Yes
 Power Assist
20A
 Auto Transfer Switch (A)
30A
 Multi-purpose Relay
3 relays
 Protection
Output short circuit,
Overload,
  Battery overvoltage,
Battery undervoltage,
Battery reverse polarity detection,
Over temperature,
High input voltage ripple
 Common Characteristics
Operating temperature range: -20°C to +50°C
(fan assisted cooling) Humidity: max 95% (non condensing)
 Weight (kg)
48.1kg
46.5kg
 Dimensions (L x W x H) mm
590 x 480 x 630 mm
 OPTIONS
 Solar Charger
SCC Series PM-SCC-45A-1248 / PM-SCC-60A-1248
(Max. 10 sets for parallel connection)
 Remote Controller
 Remote monitoring available, optional cables: 3M/15M
 Battery Temperature Sensor (BTS)
Compensation for the battery charging voltage and current