Product Name : PM-6006MS-LCD
    Product Description

    Multiple Microprocessor design base
    Detachable control panel with LCD
    Unity input power factor and wide input range
    Robust design with output transformer
    True sine-wave double conversion on-line UPS
    DC start and automatic self-diagnostic function
    Capacity of battery unlimited and alarm silent
    RS232 communication port and built-in SNMP slot
    High efficiency design to save electricity
    Low heat dissipation in long term operation
    Designed to operate under harsh environment
    Enhanced protections against lighting surges, disturbances etc..

    Advanced Power Protection for Enterprise Network.


    CAPACITY Capacity 6KVA / 4200W
    INPUT Nominal Voltage 1P2W 220Vac
    Voltage Range 176~276Vac +/- 3Vac
    Frequency 50Hz or 60Hz +/- 8%
    Power Factor >= 0.98
    OUTPUT Voltage 220Vac +/- 1% (230V or 240V re-settable via LCD panel)
    Frequency 50Hz or 60Hz +/- 8% Synchronized (Line Mode)                          
    50Hz or 60Hz +/-0.5% (Battery Mode)
    Wave-form True Sine wave
    Distortion (Tower) =<2% THD (Linear Load), =<6% THD (Non-Linear Load)
    Distortion (Rack) <4% THD (Linear Load), <7% THD (Non-Linear Load)
    Crest Ratio 3:1
    BATTERY Type Maintenance free sealed lead-acid battery
    Capacity 12V / 7Ah * 20pcs
    Charger (Option) Built-In 4.2A Charger
    Built-In Charger 2A
    Back-up (Full/Half load) 8 min.
    BYPASS Automatic Overload and UPS failure
    Transfer Time 0 ms( AC to DC & Inverter to Bypass)
    INDICATOR UPSERVER       (LCD Series) LCD UPS status, I/P&O/P Voltage& Frequency, Load %,Battery Voltage, Temperature, Event Log
    LED Normal (Green), Warning (Yellow), Fault (Red)
    Display               (LED Series) LED AC input (Green), Bypass (Yellow), Battery Low (Yellow), Inverter (Green), Load% (5 LEDs), Battery % (5 LEDs), Fault (Red)
    AUDIBLE ALARM Battery Mode Beeping every 4 seconds
    Battery Low Beeping every seconds
    Overload Beeping twice per second
    Fault Beeping Continuously
    INTERFACE RS-232 Interface UPSilon 2000 monitoring software
    SNMP For Net Agent II (Option) with SNMP manager and Web browser
    NETWORK Surge Protection RJ45 I/O port available for 10 base-T network or Fax / Modem
    ENVIRONMENT Temperature 0-40 degree C; 32-104 degree F
    Humidity 20-90% non-condensing
    Acoustic Noise Less than 55dBA (at 1 meter)
    NET WEIGHT w/o battery 90kgs
    w/ battery 18.3kgs
    Dimension (WxHxD) mm Tower Case 260 x 717 x 570
    Rack Case (2U) 482.6 x 132 x 600