PM-9030CS
Enlargement
    Product Name : PM-9030CS
    Inquiry
    Product Description

    Character:
    Advanced technology of PWM, DSP and IGBT switching components Designed to use a high frequency, highly efficiency DSP/IGBT and PWM technology in converting DC to AC power.
    True Galvanic isolation design Solve ultimately the problem of power system, including noise, lightning, and leakage current etc.
    Multi-CPU design and software/hardware cooperate control Make the system extremely high reliable.
    Plug & Play modular design To allow for each power circuit to be easily removed for quick maintenance and troubleshooting.
    Each phase with individual inverter supporting Characteristics will not be violated under 100% unbalance load.
    Protection against detaching and floating of the neutral of input power supply Ensure the safety and stability of the UPS power output.
    Protection from user error Advanced circuitry prohibits damage to the system when the user makes an operational mistake.
    Intelligent charger with temperature compensation Prolong the battery life expectancy. And with huge charging power (selectable), can charge very big capacity, long back-up time battery bank.
    Intelligent, safe battery test circuitry Test the battery without the risk of output AC failure in case of battery bad. And with battery fluid leakage and improper grounding detect circuitry, can ensure safety of the battery bank.
    ntelligent fan speed control Increase the fan life expectancy and reduce audible noise.
    Reasonable heat evacuation passage design Main PCBs are designed in a holder to separate the control circuitry and power circuitry. Therefore, the UPS system can operate under harsh environment.
    Cool start function Can be started without AC mains (with battery only) and protected from high inrush current.
    Variety of accessory (options) Remote control panel, 3 phases software for PC monitoring, auto dialing module, battery monitoring module, 3 phases SNMP card, and emergency power-off switch are available.
    Microprocessor design base
    Mini- remote control panel (option)
    Multiple output sockets
    Minimum foot print area design, light weight
    Built-In AVR for wider input range
    Auto re-charging whenever AC exist.
    Hot swappable battery by users
    RS232 communication port
    Tel/modem internet surge suppression
    DC Start function
    Green power function
    Auto detecting frequency 12-Pulse Full Controlled Rectifier (option) To reduce total harmonic current and for UPS.

    Description:
    3 phase in 3 phase out online UPS. 
    Intelligent, digitalized, and true galvanic isolation online design for Power Plants. 


    Specifications:

    MODEL PM-9030CS
    CAPACITY Capacity 30KVA / 24KW
    INPUT (RECTIFIER) Input Voltage 220 / 380 / 460, 208/ 380, 400, 415
    Input Range ±20% ( > ±20% is available upon request)
    Input Frequency 50 / 60 Hz ± 5Hz
    Power Walk In 0% - 100% : 20 sec
    Efficiency  98%
    Voltage Regulation ±1%
    BATTERY Battery Type / Pcs Maintenance free lead-acid batteries / 12V x 29pcs
    Maximum Charge
    Current Adc (Selectable)
    15
    Battery Start Yes, UPS can be started without AC source.
    INVERTER Output Voltage 220 / 380 / 460, 208 / 380, 400, 415  ± 1 %
    Wave Form Sine Wave
    Output Power Factor 0.8
    Frequency Lock Range 50 / 60 Hz ± 3Hz
    Output Frequency
    (Free Running)
    50 / 60 Hz ± 0.1 Hz
    Phase Shift Under 100% Unbalance Load < 0.5
    THD (Linear Load) < 2 %
    Overload <110% Continuous
    Overload 110-125% 15 minutes
    Overload 125-150% 10 minutes
    Overload >150% 1 minute
    Efficiency (100% Load) 93%
    STATIC SWITCH Voltage Range 173-277 VAC (L-N)
    Mains ¡÷ Inverter 
    Inverter ¡÷ Mains
    0 ms
    OVERALL CHARACTERISTICS Overall Efficiency 91%
    Maximum Heat 
    Dissipation (Kw)
    1.9
    Height x Width x Depth (mm) 1600 x 550 x 800
    Weight 
    (Kg, without battery)
    300
    Audible Noise < 65 dBA (At 1 M)
    Temperature 0-40(32-104)
    Humidity 0% - 90% (Non-Condensing)
    Altitude  
    EN50091-1,-2 YES
    Short Circuit Protection YES
    Lightning / EMC Filter MOV / Input&Output (FCC CLASS A)
    Galvanic Isolation Input&Output true Galvanic isolation
    LED, LCD, Buzzer YES
    Remote Control / 
    Communication Interface
    Monitoring 1~99 UPS simultaneously / Dry contact, RS232, RS485