PM-WCC-100AM-1248
Enlargement
Product Name : PM-WCC-100AM-1248
Inquiry
Product Description

Character:
Battery charge management; state of charge infromation.
Built-in Battery Energy Monitor tracks Power production and consumption to calculate the energy remaining in battery state of charge (SOC) is displayed in percent full; Amp-hours; Watt-hours; and 90days of energy-harvest history is stored in the wind charger.
Continuous output Power Rating without de-rating at up to 50°C ambient temperature.
Supports Flooded Lead Acid (FLA); GEL; and Absorbed Glass Mat (AGM) batteries; 2/3/4 Stage charging with adjustable set point.
Input acceptance up to 220VAC or 240VDC normal (240VDC Max).
Built-in temperature compensation function for safe and complete charging.

Description:
Optimal Wind Maximum Power Point Tracking
Wind & Solar Charge Controller
Can be paralleled (Max. 16 sets) at will; according to your demand.

Specifications:

  MODEL PM-WCC-100AM-1248
  ELECTRICAL
  Input Voltage Range (no damage) 0 ~ 220 VAC
  Operating Input Voltage Range from PMG
  (Permanent Magnet Generator)
20 ~ 220 VAC
0 ~ 600 Hz
Optimal Range: 20 ~ 180 VAC
  System voltage ratings 12; 24; 36; 48 VDC
  Current ratings-Battery Charge Control 100A
  Max. Current in the Brake Resistor 100A
Diversion load
  DC Input Voltage Range 16 ~ 240 VDC Operating
240 VDC Maximum
  Automatic Brake Function 5 Level:
200; 210; 220; 230; 240 VDC
(Adjustable)
Can be customized for the wind turbines
  Maximum Wind Turbine Capacity
Charging 48 VDC Batteries 6.0KW
Charging 36 VDC Batteries 4.5KW
Charging 24 VDC Batteries 3.0KW
Charging 12 VDC Batteries 1.5KW
  Charge Regulation Modes Bulk; Absorption; Float; Auto/ Manual Equalization
  Battery Temperature Compensation 5.0 mV per °C ; per 2 volt cell
  DC to DC Conversion Capability 12V Battery: 16~240VDC
24V Battery: 32~240VDC
36V Battery: 48~240VDC
48V Battery: 64~240VDC
  Display Status Built-in 2-line; 20-character LCD with backlight
LCD status screen displays input voltage and
current; output voltage and current; charge-mode;
Battery SOC
  Data Logging Logs energy harvested for 90 days; LCD displays WH; KWH; AH
  Energy Monitor LCD shows SOC; AH; WH; and present charge or discharge current. A 50mV/ 500Amp shunt is required to use
  Auxiliary Relays Two independent relays with from A (SPST) contacts for control of external devices. Contact rating is 3 Amps; 50VDC
  Operation Temperature Full Power Output to +50 °C ambient
  Standby Power < 2 Watts
  Relative Humidity 0 ~ 100% condensing
  MECHANICAL
  Dimensions (mm) [H x W x L] 401 x 258 x 183
  Weight 8.3 kg
  Optional Diversion Load  
  Specifications subject to change without notice